Air Insulated Switchgear up to 17.5 kV (Localized with IMS), Vacuum withdrawable circuit breaker
PiX range is an indoor switchgear assembly that provides maximum user safety. It is intended to meet all electrical distribution needs and incorporates a set of innovative solutions.
Features
It is compact in design and uses vacuum circuit breakers.
- Ratings up to 4,000 A / 40 kA for 12 kV and 17.5 kV range
- Insulated Busbars
- Loss of Service Continuity – LSC 2B PM
- Floor, top or rear cable connection
- Back-to-wall or rear access configurations
- Current and voltage transformers on busbar or cable side
Internal Arc Classification (IAC) AFLR duration 1 s according to IEC62271-200
Benefits
- Space saving, flexible cubicle width and back-to-wall installation
- Safe and reliable with a full 1 second Internal Arc Classification – AFLR
- Comprehensive interlocking, with all operations from the front
- Can be fully installed from the front of the cubicle
- Environmentally compatible, easy to recycle
Applications
Energy: HV/MV substations, MV/MV substations, wind farms
Infrastructure: hospital, airports, subways, railways
Industries: oil, cement, mine
The cubicle
The high voltage part of the cubicle is separated in 3 compartments using metal partitions (PM class):
- Busbars compartment
- Cables compartment
- Compartment for switching device
Each compartment is connected to earth. These partitions are defined Loss of Service Category class “LSC2B-PM” by IEC standard IEC 62271-200: 2011.
Rated voltage | Ur | Kv | 12 | 17.5 |
Rated power frequency withstand voltage – 1 min | Ud | kV | 28 | 38 |
Rated lightening impulse withstand voltage – peak | Up | Kv | 75 | 95 |
Rated frequency | f | Hz | 50160 | 50/60 |
Rated short circuit breaking current | Isc | KA | Up to 40 | Up to 40 |
Rated peak withstand current | 1p ©50Hz | KA | 100 | 100 |
1p ©50Hz | KA | 104(2) | 104(2) | |
Rated duration of short circuit | tk | s | 3 | 3 |
Rated current busbar, max | Ir bb | A | up to 4000 (1) | up to 4000 CO |
Ir | A | 630 | 630 | |
Ir | A | 1250 | 1250 | |
Ir | A | 2000 | 2000 | |
Ir | A | 2500 | 2500 | |
Ir | A | 3150 | 3150 | |
Ir | A | 4000 CO | 4000 (1) | |
Rated current contactor (see detail in PIX-M) | Ir | A | 196 | NA |
Rated current switch disconnector | Ir | A | 630 | 630 |
Internal arc classification
Internal arc | lsc | KA | 40 | 40 |
Arc duration | t | s | 1 | 1 |
Classification | AFLR | IP2X |
Degree Of Protection
Enclosure | Standard Option | IP3X | IP3X |
IP4X | IP4X | ||
Between Compartments | IP2X | IP2X |
Standards IEC
The PIX meet the following international standards:
- IEC 62271-1: 2017: High-voltage switchgear and control gear: common specifications
- IEC 62271-200: 2011: AC metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and including 52 kA
- IEC 62271-100: 2008: High-voltage switchgear and controlgear – Alternating current circuit-breakers
- IEC 62271-106: 2011: High-voltage switchgear and controlgear – Alternating current contactors, contactor-based controllers and motor-starters
- IEC 60282-1: 2020: High-voltage fuses – Current-limiting fuses
- IEC 62271-102: 2018: High-voltage switchgear and controlgear – Alternating current disconnectors and earthing switches
- IEC 60255-1: 2009: Measuring relays and protection equipment – Common requirements
- IEC 61869-2: 2012: Instrument transformers
- Current transformers
- IEC 61869-3: 2011: Instrument transformers
- Inductive voltage transformers
- IEC 60044-8: 2008: Instrument transformers
- Electronic current transformers